Parameter
1501 AO1
CONTENT SEL
SYSTEM CONTROL INPUTS
1601 RUN ENABLE
1604 FAULT RESET
SEL
1606 LOCAL LOCK
1607
PARAM SAVE
1608 START
ENABLE 1
1609 START
ENABLE 2
LIMITS
2013 MIN TORQUE
SEL
2014 MAX TORQUE
SEL
2201 ACC/DEC 1/2
SEL
2209 RAMP INPUT 0 COMM
COMMUNICATION FAULT FUNCTIONS
3018 COMM FAULT
FUNC
3019 COMM FAULT
TIME
PID CONTROLLER REFERENCE SIGNAL SOURCE SELECTION
4010
SET POINT
/411
SEL
0/42
10
Setting for
fieldbus control
135 (ie,
0135
COMM VALUE
1)
COMM
COMM
COMM
DONE
SAVE...
COMM
COMM
COMM
COMM
COMM
NOT SEL
FAULT
CONST SP 7
LAST SPEED
0.1 ... 60.0 s
COMM
COMM+AI1
COMM*AI1
Fieldbus control with fieldbus adapter 343
Function/Information
Directs the contents of fieldbus reference
COMM VALUE 1
to analog output AO.
Selects the fieldbus interface as the source for
the inverted Run enable signal (Run disable).
Selects the fieldbus interface as the source for
the fault reset signal.
Selects the fieldbus interface as the source for
the local lock signal.
Saves parameter value changes (including
those made through fieldbus control) to the
permanent memory.
Selects the fieldbus interface as the source for
the inverted Start enable 1 (Start disable)
signal.
Selects the fieldbus interface as the source for
the inverted Start enable 2 (Start disable)
signal.
Selects the fieldbus interface as the source for
the minimum torque limit 1/2 selection.
Selects the fieldbus interface as the source for
the maximum torque limit 1/2 selection.
Selects the fieldbus interface as the source for
acceleration/deceleration ramp pair 1/2
selection
Selects the fieldbus interface as the source for
forcing ramp input to zero.
Determines the drive action in case the fieldbus
communication is lost.
Defines the time between the communication
loss detection and the action selected with
parameter
3018 COMM FAULT
PID control reference (REF2)
0135
FUNC.