All parameters
No.
Name/Value
2606 SWITCHING
FREQ
4 kHz
8 kHz
12 kHz
16 kHz
2607 SWITCH FREQ
CTRL
ON
Description
Defines the switching frequency of the drive. Higher
switching frequency results in lower acoustic noise.
In multimotor systems, do not change the switching
frequency from the default value.
See also parameter
2607 SWITCH FREQ CTRL
section
Switching frequency derating, I2N
Sets the switching frequency to 4 kHz.
Sets the switching frequency to 8 kHz.
Sets the switching frequency to 12 kHz.
Sets the switching frequency to 16 kHz.
Selects the control method for the switching frequency.
Selection has no effect if parameter
FREQ
is 4 kHz.
Drive maximum current is automatically derated according
to the selected switching frequency (see parameter
SWITCH FREQ CTRL
derating, I2N
on page 376) and adapted according to the
drive temperature.
It is recommended to use this selection when a specific
switching frequency is required with maximum performance.
f
limit
sw
16 kHz
4 kHz
80...100 °C *
* Temperature depends on the drive output frequency.
Actual signals and parameters 243
on page 376.
2606 SWITCHING
and section
Switching frequency
100...120 °C *
Def/FbEq
4 kHz
and
1 = 1 kHz
ON
(LOAD)
1
2607
Drive
temperature
T