316 Fieldbus control with embedded fieldbus
The new settings will take effect when the drive is next powered up, or when
parameter
5302 EFB STATION ID

Drive control parameters

After the Modbus communication has been set up, the drive control parameters listed
in the table below should be checked and adjusted when necessary.
The Setting for fieldbus control column gives the value to use when the Modbus
interface is the desired source or destination for that particular signal. The
Function/Information column gives a description of the parameter.
Parameter
CONTROL COMMAND SOURCE SELECTION
1001 EXT1
COMMAND
S
1002 EXT2
COMMAND
S
1003 DIRECTION
1010 JOGGING
SEL
1102 EXT1/EXT2
SEL
1103 REF1
SELECT
setting is cleared and reset.
Setting for
Function/Information
fieldbus
control
COMM
Enables
0...1 (STOP/START) when EXT1 is
selected as the active control
location.
COMM
Enables
0...1 (STOP/START) when EXT2 is
selected as the active control
location.
FORWARD
Enables the rotation direction control
REVERSE
as defined by parameters
REQUEST
1002. The direction control is
explained in section
handling
COMM
Enables jogging 1 or 2 activation
through
20...21
COMM
Enables EXT1/EXT2 selection
through
(EXT2); with the ABB drives profile
5319 EFB PAR 19
LOC).
COMM
Fieldbus reference REF1 is used
COMM+AI
when EXT1 is selected as the active
1
control location. See section
COMM*AI1
Fieldbus references
information on the alternative
settings.
0301 FB CMD WORD 1
0301 FB CMD WORD 1
1001
Reference
on page 323.
0302 FB CMD WORD 2
(JOGGING 1
/
JOGGING
0301 FB CMD WORD 1
bit 11
(EXT CTRL
on page
Modbus register
address
ABB
DCU
DRV
bits
40031
bits 0...1
bits
40031
bits 0...1
40031
and
bit 2
40032
bits
bits
2).
20...21
40001
40031
bit 5
bit 11
bit 5
40002 for REF1
320
for