ABB ACS355 series User Manual page 361

Hide thumbs Also See for ACS355 series:
Table of Contents

Advertisement

CODE FAULT
0012
MOTOR STALL
(7121)
0305
bit 11
(programmable
fault function
3010...3012)
0014
EXT FAULT 1
(9000)
0305
bit 13
(programmable
fault function
3003)
0015
EXT FAULT 2
(9001)
0305
bit 14
(programmable
fault function
3004)
0016
EARTH FAULT
(2330)
0305
bit 15
(programmable
fault function
3017)
0017
UNDERLOAD
(FF6A)
0306
bit 0
(programmable
fault function
3013...3015)
0018
THERM FAIL
(5210)
0306
bit 1
0021
CURR MEAS
(2211)
0306
bit 4
CAUSE
Motor is operating in stall
region due to, eg,
excessive load or
insufficient motor power.
External fault 1
External fault 2
Drive has detected earth
(ground) fault in motor or
motor cable.
Drive internal fault.
Motor load is too low due
to, eg, release
mechanism in driven
equipment.
Temperature of the drive
exceeds the operating
level of the thermistor.
Drive internal fault.
Thermistor used for drive
internal temperature
measurement is open or
short-circuited
Drive internal fault.
Current measurement is
out of range.
Fault tracing 361
WHAT TO DO
Check motor load and drive ratings.
Check fault function parameters
3010...3012.
Check external devices for faults.
Check parameter
3003 EXTERNAL
FAULT 1
setting.
Check external devices for faults.
Check parameter
3004 EXTERNAL
FAULT 2
setting.
Check motor.
Check motor cable. Motor cable
length must not exceed maximum
specifications. See section
connection data
on page 385.
Note: Disabling earth fault (ground
fault) may damage drive.
Internal short-circuit may cause earth
fault indication. This has happened if
fault
0001
appears after disabling the
earth fault. Replace the drive.
Check for problem in driven
equipment.
Check fault function parameters
3010...3012.
Check motor power against drive
power.
Check that the ambient temperature is
not too low.
Replace the drive.
Replace the drive.
Motor