Supervisions

The drive monitors whether certain user selectable variables are within the user-
defined limits. The user may set limits for speed, current etc. The supervision status
can be indicated through relay or digital output.
The supervision functions operate on a 2 ms time level.
Settings
Parameter group
32 SUPERVISION
Diagnostics
Actual signal
1401
1402/1403/1410
1805
8425,
8426
/ 8435, 8436 /.../8495,
8496
Parameter lock
The user can prevent parameter adjustment by activating the parameter lock.
Settings
Parameters
1602 PARAMETER LOCK
PID control
There are two built-in PID controllers in the drive:
• Process PID (PID1) and
• External/Trim PID (PID2).
The PID controller can be used when the motor speed needs to be controlled based
on process variables such as pressure, flow or temperature.
When the PID control is activated, a process reference (setpoint) is connected to the
drive instead of a speed reference. An actual value (process feedback) is also
brought back to the drive. The drive compares the reference and the actual values,
and automatically adjusts the drive speed in order to keep the measured process
quantity (actual value) at the desired level (reference).
The control operates on a 2 ms time level.
Additional information
Supervision status through RO 1
Supervision status through RO 2...4. With option
MREL-01 only.
Supervision status through DO
Sequence programming state change according to
supervision functions
and
1603 PASS CODE
Program features 151