ABB ACS355 series User Manual page 340

Hide thumbs Also See for ACS355 series:
Table of Contents

Advertisement

340 Fieldbus control with fieldbus adapter
Drive
The drive can be set to receive all of its control information through the fieldbus
interface, or the control can be distributed between the fieldbus interface and other
available sources, eg, digital and analog inputs.
The drive can communicate to a control system through a fieldbus adapter using, for
example, the following serial communication protocols. Other protocols may be
available; contact your local ABB representative.
• PROFIBUS-DP (FPBA-01 adapter)
• CANopen (FCAN-01 adapter)
• DeviceNet™ (FDNA-01 adapter)
• Ethernet (FENA-01 adapter)
• Modbus RTU (FMBA-01 adapter. See chapter
fieldbus
on page 313.)
The drive detects automatically which fieldbus adapter is connected to the drive
terminal X3 (with the exception of FMBA-01). The DCU profile is always used in
communication between the drive and the fieldbus adapter (see section
control interface
on page 344). The communication profile on the fieldbus network
depends on the type and settings of the connected adapter.
The default profile settings are protocol-dependent (for example, vendor-specific
profile (ABB drives) for PROFIBUS and industry-standard drive profile (AC/DC Drive)
for DeviceNet).
X3
Fieldbus
adapter
Data flow
Control word (CW)
References
Status word (SW)
Actual values
Parameter R/W
requests/responses
Fieldbus
controller
Fieldbus
Other
devices
Process I/O (cyclic)
Service messages (acyclic)
Fieldbus control with embedded
Fieldbus

Hide quick links: