Diagnostics
Actual signal
Groups
01 OPERATING DATA
04 FAULT HISTORY
Motor identification
The performance of vector control is based on an accurate motor model determined
during the motor start-up.
A motor Identification magnetization is automatically performed the first time the start
command is given. During this first start-up, the motor is magnetized at zero speed
for several seconds to allow the motor model to be created. This identification method
is suitable for most applications.
In demanding applications a separate Identification run (ID run) can be performed.
Settings
Parameter
9910 ID RUN
Additional information
...
Lists of actual signals
Program features 137