ABB ACS355 series User Manual page 305

Hide thumbs Also See for ACS355 series:
Table of Contents

Advertisement

All parameters
No.
Name/Value
ENTER
SETPNT
AT SETPOINT
AI1 L1 & DI5
AI2 L2 & DI5
AI1 H1 & DI5
AI2 H2 & DI5
AI1 L1 & DI4
AI2 L2 & DI4
AI1 H1 & DI4
AI2 H2 & DI4
DLY AND DI1
DLY AND DI2
DLY AND DI3
DLY AND DI4
DLY AND DI5
DLY & AI2 H2
DLY & AI2 L2
DLY & AI1 H1
Description
State change when drive output frequency/speed enters the
reference area (ie, the difference is less than or equal to 4%
of the maximum reference).
State change when drive output frequency/speed equals the
reference value (= is within tolerance limits, ie, the error is
less than or equal to 1% of the maximum reference).
State change when AI1 value < par.
and when DI5 is active.
State change when AI2 value < par.
value and when DI5 is active.
State change when AI1 value > par.
value and when DI5 is active.
State change when AI2 value > par.
value and when DI5 is active.
State change when AI1 value < par.
value and when DI4 is active.
State change when AI2 value < par.
value and when DI4 is active.
State change when AI1 value > par.
value and when DI4 is active.
State change when AI2 value > par.
value and when DI4 is active.
State change when delay time defined by parameter
ST1 CHANGE DLY
has elapsed and DI1 is active.
State change when delay time defined by parameter
ST1 CHANGE DLY
has elapsed and DI2 is active.
State change when delay time defined by parameter
ST1 CHANGE DLY
has elapsed and DI3 is active.
State change when delay time defined by parameter
ST1 CHANGE DLY
has elapsed and DI4 is active.
State change when delay time defined by parameter
ST1 CHANGE DLY
has elapsed and DI5 is active.
State change when delay time defined by parameter
ST1 CHANGE DLY
has elapsed and AI2 value > par.
SEQ VAL 2 HIGH
value.
State change when delay time defined by parameter
ST1 CHANGE DLY
has elapsed and AI2 value < par.
SEQ VAL 2 LOW
value.
State change when delay time defined by parameter
ST1 CHANGE DLY
has elapsed and AI1 value > par.
SEQ VAL 1 HIGH
value.
Actual signals and parameters 305
8412 SEQ VAL 1 LOW
8414 SEQ VAL 2 LOW
8411 SEQ VAL 1 HIGH
8413 SEQ VAL 2 HIGH
8412 SEQ VAL 1 LOW
8414 SEQ VAL 2 LOW
8411 SEQ VAL 1 HIGH
8413 SEQ VAL 2 HIGH
Def/FbEq
51
52
53
54
55
56
57
58
59
60
8424
61
8424
62
8424
63
8424
64
8424
65
8424
66
8413
8424
67
8414
8424
68
8411

Hide quick links: