Earth Fault Protection - ABB ACS355 series User Manual

Hide thumbs Also See for ACS355 series:
Table of Contents

Advertisement

Settings
Parameters
3013 UNDERLOAD
UNDERLOAD CURVE

Earth fault protection

The Earth fault protection detects earth faults in the motor or motor cable. The
protection can be selected to be active during start and run or during start only.
An earth fault in the input power line does not activate the protection.
Settings
Parameter
3017 EARTH FAULT
Incorrect wiring
Defines the operation when incorrect input power cable connection is detected.
Settings
Parameter
3023 WIRING FAULT
Input phase loss
Input phase loss protection circuits supervise the input power cable connection status
by detecting intermediate circuit ripple. If a phase is lost, the ripple increases.
Settings
Parameter
3016 SUPPLY PHASE
Pre-programmed faults
Overcurrent
The overcurrent trip limit for the drive is 325% of the drive nominal current.
DC overvoltage
The DC overvoltage trip limit is 420 V (for 200 V drives) and 840 V (for 400 V drives).
DC undervoltage
The DC undervoltage trip limit is adaptive. See parameter
Drive temperature
The drive supervises the IGBT temperature. There are two supervision limits: Alarm
limit and fault trip limit.
FUNC,
3014 UNDERLOAD TIME
Program features 149
and
3015
2006 UNDERVOLT
CTRL.