4. Find the appropriate parameter in the group with
keys
/
5. Press and hold
parameter value is shown with
6. Change the value with keys
changes faster while you keep the key pressed
down.
7. Save the parameter value by pressing
Select the application macro (parameter 9902)
according to how the control cables are
connected.
The default value 1
most cases.
Select the motor control mode (parameter 9904).
1
(VECTOR:
SPEED) is suitable in most cases.
2
(VECTOR:
TORQ) is suitable for torque control
applications.
3
(SCALAR:
FREQ) is recommended
• for multimotor drives when the number of the motors
connected to the drive is variable
• when the nominal motor current is less than 20% of
the nominal current of the drive
• when the drive is used for test purposes with no
motor connected.
3
(SCALAR:
FREQ) is not recommended for
permanent magnet synchronous motors.
Enter the motor data from the motor nameplate.
Asynchronous motor nameplate example:
ABB Motors
3
motor
M2AA 200 MLA 4
IEC 200 M/L 55
Hz
kW
V
690 Y
30
50
400 D
50
30
660 Y
50
30
380 D
30
50
50
415 D
30
35
440 D
60
Cat. no
3GAA 202 001 - ADA
6312/C3
.
for about two seconds until the
under the value.
SET
/
(ABB
STANDARD) is suitable in
No
Ins.cl. F
IP 55
IA/IN t E/s
r/min
A
cos
1475
32.5
0.83
1475
56
0.83
1470
34
0.83
1470
59
0.83
1475
54
0.83
59
0.83
1770
6210/C3
180
IEC 34-1
REM
REM
. The value
REM
.
REM
REM
REM
Note: Set the motor data to
exactly the same value as on
the motor nameplate. For
example, if the motor nominal
speed is 1470 rpm on the
nameplate, setting the value of
parameter
SPEED
to 1500 rpm results in
the wrong operation of the
drive.
380 V
supply
voltage
9903
PAR
FWD
1
PAR
SET
FWD
2
PAR
SET
FWD
9903
PAR
FWD
9902
PAR
FWD
9904
PAR
FWD
9908 MOTOR NOM