ABB ACS355 series User Manual page 309

Hide thumbs Also See for ACS355 series:
Table of Contents

Advertisement

All parameters
No.
Name/Value
USER S1
LOAD
USER S1
SAVE
USER S2
LOAD
USER S2
SAVE
USER S3
LOAD
USER S3
SAVE
9903 MOTOR TYPE Selects the motor type.
AM
PMSM
9904 MOTOR CTRL
MODE
VECTOR:
SPEED
VECTOR:
TORQ
SCALAR:
FREQ
Description
User 1 macro loaded into use. Before loading, check that
the saved parameter settings and the motor model are
suitable for the application.
Save User 1 macro. Stores the current parameter settings
and the motor model.
User 2 macro loaded into use. Before loading, check that
the saved parameter settings and the motor model are
suitable for the application.
Save User 2 macro. Stores the current parameter settings
and the motor model.
User 3 macro loaded into use. Before loading, check that
the saved parameter settings and the motor model are
suitable for the application.
Save User 3 macro. Stores the current parameter settings
and the motor model.
Cannot be changed while the drive is running.
Asynchronous motor. Three-phase AC voltage-supplied
induction motor with squirrel cage rotor.
Permanent magnet synchronous motor. Three-phase AC
voltage-supplied synchronous motor with permanent
magnet rotor and sinusoidal back emf voltage.
Selects the motor control mode.
Sensorless vector control mode.
Reference 1 = speed reference in rpm.
Reference 2 = speed reference as a percentage. 100% is
the absolute maximum speed, equal to the value of
parameter
2002 MAXIMUM SPEED
SPEED
if the absolute value of the minimum speed is
greater than the maximum speed value).
Vector control mode.
Reference 1 = speed reference in rpm.
Reference 2 = torque reference as a percentage. 100%
equals nominal torque.
Scalar control mode.
Reference 1 = frequency reference in Hz.
Reference 2 = frequency reference as a percentage. 100%
is the absolute maximum frequency, equal to the value of
parameter
2008 MAXIMUM FREQ
FREQ
if the absolute value of the minimum speed is greater
than the maximum speed value).
Actual signals and parameters 309
(or
2001 MINIMUM
(or
2007 MINIMUM
Def/FbEq
0
-1
-2
-3
-4
-5
AM
1
2
SCALAR:
FREQ
1
2
3

Hide quick links:

Advertisement

Table of Contents
loading