352 Fault tracing
CODE ALARM
2010
MOTOR TEMP
0308
bit 9
(programmable fault
function
3005...3009
2011
UNDERLOAD
0308
bit 10
(programmable fault
function
3013...3015)
2012
MOTOR STALL
0308
bit 11
(programmable fault
function
3010...3012)
2013
AUTORESET
1)
0308
bit 12
2018
PID SLEEP
1)
0309
bit 1
(programmable fault
function 1610)
2019
ID RUN
0309
bit 2
2021
START ENABLE 1
MISSING
0309
bit 4
2022
START ENABLE 2
MISSING
0309
bit 5
2023
EMERGENCY
STOP
0309
bit 6
CAUSE
Motor temperature is
too high (or appears to
be too high) due to
excessive load,
insufficient motor
/ 3503)
power, inadequate
cooling or incorrect
start-up data.
Measured motor
temperature has
exceeded alarm limit
set by parameter
ALARM
LIMIT.
Motor load is too low
due to, eg, release
mechanism in driven
equipment.
Motor is operating in
stall region due to, eg,
excessive load or
insufficient motor
power.
Automatic reset alarm
Sleep function has
entered sleeping
mode.
Motor Identification run
is on.
No Start enable 1
signal received
No Start enable 2
signal received
Drive has received
emergency stop
command and ramps
to stop according to
ramp time defined by
parameter
2208
EMERG DEC
WHAT TO DO
For more information, see fault
in
Fault messages generated by the
drive
on page 357.
3503
Check for problem in driven
equipment.
Check fault function parameters.
Check motor power against drive
power.
Check motor load and drive ratings.
Check fault function parameters.
Check parameter group
AUTOMATIC RESET
See parameter groups
PID SET
1...
2.
This alarm belongs to normal start-up
procedure. Wait until drive indicates
that motor identification is completed.
Check parameter
ENABLE 1
Check digital input connections.
Check fieldbus communication
settings.
Check parameter
ENABLE 2
Check digital input connections.
Check fieldbus communication
settings.
Check that it is safe to continue
operation.
Return emergency stop push button to
normal position.
TIME.
0009
31
settings.
40 PROCESS
41 PROCESS PID SET
1608 START
settings.
1609 START
settings.