CODE FAULT
0030
FORCE TRIP
(FF90)
0306
bit 13
0034
MOTOR PHASE
(FF56)
0306
bit 14
0035
OUTP WIRING
(FF95)
0306
bit 15
(programmable
fault function
3023)
0036
INCOMPATIBLE
SW
(630F)
0307
bit 3
0037
CB OVERTEMP
(4110)
0305
bit 12
0044
SAFE TORQUE
OFF
(FFA0)
0307
bit 4
0045
STO1 LOST
(FFA1)
0307
bit 5
0046
STO2 LOST
(FFA2)
0307
bit 6
CAUSE
Trip command received
from fieldbus
Motor circuit fault due to
missing motor phase or
motor thermistor relay
(used in motor
temperature
measurement) fault.
Incorrect input power
and motor cable
connection (ie, input
power cable is
connected to drive motor
connection).
Loaded software is not
compatible.
Drive control board
overheated. Fault trip
limit is 95 °C.
STO (Safe torque off)
requested and it
functions correctly.
Parameter
3025 STO
OPERATION
is set to
react with fault.
STO (Safe torque off)
input channel 1 has not
de-energized, but
channel 2 has. Opening
contacts on channel 1
might have been
damaged or there is a
short-circuit.
STO (Safe torque off)
input channel 2 has not
de-energized, but
channel 1 has. Opening
contacts on channel 2
might have been
damaged or there is a
short-circuit.
Fault tracing 363
WHAT TO DO
Fault trip was caused by fieldbus. See
fieldbus user's manual.
Check motor and motor cable.
Check motor thermistor relay (if used).
Possible power wiring error detected.
Check that input power connections
are not connected to drive output.
Fault can be declared if input power is
delta grounded system and motor
cable capacitance is large. This fault
can be disabled by parameter
WIRING
FAULT.
Loaded software is not compatible
with the drive. Contact your local ABB
representative.
Check for excessive ambient
temperature.
Check for fan failure.
Check for obstructions in air flow.
Check the dimensioning and cooling
of cabinet.
If this was not expected reaction to
safety circuit interruption, check
cabling of safety circuit connected to
STO terminals X1C.
If different reaction is required, change
value of parameter
3025 STO
OPERATION.
Reset fault before starting.
Check STO circuit cabling and
opening of contacts in STO circuit.
Check STO circuit cabling and
opening of contacts in STO circuit.
3023