Commissioning; Alarms - Siemens SINUMERIK 840D sl Function Manual

Safety integrated
Hide thumbs Also See for SINUMERIK 840D sl:
Table of Contents

Advertisement

Commissioning

10.1

Alarms

Replacing software/hardware
After hardware and/or software components have been changed or replaced, it is only
permissible to boot the system and activate the drives when the protective devices are closed.
It is not permissible that personnel are present within the danger zone.
It may be necessary to carry-out a new, partial or complete acceptance test depending on
the requirement or replacement.
Before persons may re-enter the hazardous area, the drives should be tested to ensure that
they exhibit stable behavior by briefly moving them in both the plus and minus directions (+/–).
This is especially important specifically for high-speed linear or torque motors.
SE and SN
The function "safe software limit switch" (SE) is also called "safe limit positions" and the
function "safe software cams" (SN) is also called "Safe Cams".
Activating SI functions
If SI functions SH, SBH or SG have been enabled, then they become operational after the
control system has booted (basic display on screen). For the SE and SN functions, safety-
related position evaluation is only possible after safety-related referencing has been
successfully completed.
Protection of persons
Protection of operating personnel must be the primary consideration when configuring
machine data for SINUMERIK Safety Integrated. This is this reason that the parameterizable
tolerances, limit values and delay times should be determined and optimized during the
commissioning phase dependent on the machine design and arrangement.
Safety Integrated
Function Manual, 12/2017, 6FC5397-4BP40-6BA1
WARNING
WARNING
WARNING
WARNING