Ss1 (Time-Controlled) With External Stop; Overview Of Important Parameters - Siemens SINUMERIK 840D sl Function Manual

Safety integrated
Hide thumbs Also See for SINUMERIK 840D sl:
Table of Contents

Advertisement

5.4.2

SS1 (time-controlled) with external stop

SS1 and controlled shutdown
In order to achieve stop Category 1 according to EN 60204-1 using function "SS1 (time-
controlled) with external stop (SS1E)", the higher-level control must facilitate a controlled
shutdown at the same time.
Any axis motion is possible
During the delay time (p9652), for "SS1 (time-controlled) with external stop", arbitrary axis
motion caused by the position controller is possible.
Differences between "Safe Stop 1 with OFF3 and with external stop"
"SS1 with OFF3" and "SS1 with external stop" have the following differences:
● In order to activate "SS1 with external stop", parameter p9653 must also be set = 1.
● When SS1 is selected, the drive is not braked along the OFF3 ramp, but after the delay
time has expired (p9652), only STO/SBC is automatically initiated.
5.4.3

Overview of important parameters

● p1135[0...n]
● p9652
● p9852
● r9772
● r9773
● r9774
● r9872
● p9653
Safety Integrated
Function Manual, 12/2017, 6FC5397-4BP40-6BA1
CAUTION
CAUTION
OFF3 ramp-down time
SI Safe Stop 1 delay time (Control Unit)
SI Safe Stop 1 delay time (Motor Module)
SI status (Control Unit)
SI status (Control Unit + Motor Module)
SI status (group STO) / SI stat group STO
SI status (Motor Module)
SI Safe Stop 1 braking response integrated in the drive (only for "SS1
(time controlled) without OFF3"
Safety Functions integrated in the drive
5.4 Safe Stop 1 (SS1, time-controlled)
63