Connecting sensors and actuators

8.5 Safe programmable logic

Three SPL output data are considered to be contiguous. The value is changed from 101 to
110 in both SPL programs (NCK-SPL and PLC-SPL).
Values transferred from the F_SENDDP in the F-net data telegram:
Output value
Possible inter‐
mediate value
Final value
Runtime differences
Due to runtime differences in the NCK-SPL and PLC-SPL, it cannot be guaranteed that these
are sent consistently (in time) by F_SENDDP in the F-net data telegram when several SPL
output data are simultaneously changed (NCK: $A_OUTSE, PLC: $A_OUTSEP).
8.4.16

Supplementary conditions

For SINUMERIK 840D sl, the following restrictions apply for the safety-related CPU-CPU
communication to couple plants and systems:
● The 2 integer values, defined in the F-net data area of the F-telegram, are not used or not
evaluated by the F_SENDDP and F_RECVDP realized for SINUMERIK.
● Axis specific SGE/SGA cannot be directly coupled to F_SENDDP and F_RECVDP.
● A maximum of 250 ms can be set for the F_DP clock cycle.
● The F-net data are automatically coupled to the SPL interface in DB18 by the basic PLC
program. It is not possible to couple them in a PLC user program.
8.5
Safe programmable logic
Using safe programmable logic
Using "safe programmable logic" (outside the commissioning phase) is only possible if at
least one real axis is operated with enabled and active safety functionality.
256
NCK-SPL
101
110
110
WARNING
WARNING
AND
PLC-SPL
&
101
101
&
&
110
Function Manual, 12/2017, 6FC5397-4BP40-6BA1
=
F-net data telegram
=
101
100
=
=
110
Safety Integrated