Procedure
Step 1 Determine the mounting holes for the rack environment unit in the cabinet based on the
engineering layout diagram and install floating nuts.
Step 2 Secure the rack environment unit to the cabinet by tightening the M6 screws on the left and
right mounting ears clockwise.
Figure 7-16 Installing a rack environment unit
----End
7.7 Installing Monitoring Components on a Control
Skylight
Monitoring components should be installed in the appropriate holes on the control skylight.
Issue 04 (2017-06-30)
If a ground copper bar is installed on the top of the rack rail, install a rack environment
unit at the 40 U position. A cable manager should be installed between the rack
environment unit and the ground bar.
If no ground copper bar is installed on the top of the rack rail, install a rack environment
at the top of the rack rail.