Figure A-7 Column occupying part of a cabinet place (A ≥ 800 mm and B ≥ 400 mm)
Issue 04 (2017-06-30)
Cabinet places on the column side are left blank and sealed by sealing plates. Directions of the
concave sides of the sealing plates are shown in Figure A-7.
Install cable trays over the cabinets on both sides of the blank cabinet place. If the cable trays cannot
be installed in combined mode, install them in layered mode, the upper for routing weak-current
cables while the lower for routing strong-current cables.
Install an adjustable skylight over the aisle containment. The area to be covered by the adjustable
skylight is shown in Figure A-7.