FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Single-Row
Aisle Containment, 380 V)
----End
4.2 Installing Cabinets (Without Bases)
Procedure
Step 1 Place end cabinets in the marked positions.
Figure 4-4 Placing a cabinet
Step 2 Level the cabinets. Ensure that the height deviation of all cabinets is less than 3 mm.