FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Single-Row
Aisle Containment, 380 V)
Figure A-37 Connecting cables to the industrial connector (five-core cable)
A.7 (Optional) Connecting PDU2000 Cables
Context
If the PDU2000 is not provided with industrial connectors, connect the PDU2000 cables and
lay out the cables on the cabinet top.
Procedure
Step 1 Refer to Figure A-38–Figure A-41 to connect the PDU2000 cables.
Figure A-38–Figure A-41 show only the cable connection methods. PDU2000 cable
connections depend on the PDU2000 type and wiring port silk screen.