Huawei FusionModule2000 Installation Manual page 44

Smart modular data center, 2000 mm high cabinets, single-row aisle containment, 380 v
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Single-Row
Aisle Containment, 380 V)
Applicati
on
Scenario
Indoor
unit
Outdoor
unit
(applicabl
e to
NetCol50
0-A032/03
6/NetCol5
00-A0265
S11E0)
Outdoor
unit
(applicabl
e to
NetCol50
0-A026SC
11E0)
Issue 04 (2017-06-30)
Name
Technical Specifications
Power cable
Electrical power cable, 600 V,
(optional)
ZA-RVV, 5 x 6 mm
core wires: red, yellow, green,
blue, black), 46 A, outdoor cable,
CE, 32 A
M6/OT
Bare crimp terminal, OT, 6 mm
terminal
M6, 50 A, tin plating, 12–10
AWG, yellow
Cord end
Common terminal, single cord end
terminal
terminal, 6 mm
insertion depth 12 mm, black
Signal cable
Balanced twisted pair, 100 ohm,
(optional)
SFTP CAT5E, 0.53 mm, 24 AWG,
4 pairs, black, outdoor cable
Power cable
Electronic electric cable, 600 V,
(optional)
ZA-RVV, 5 x 2.5 mm
core wires: red, yellow, green,
blue, black), 27 A, outdoor cable,
CE
M4/OT
Bare crimp terminal, OT, 2.5 mm
terminal
M4, 27 A, tin plating, 16–14 AWG
M6/OT
Bare crimp terminal, OT, 2.5 mm
terminal
M6, 27 A, tin plating, 16–14 AWG
Cord end
Bare crimp terminal, single cord
terminal
end terminal, 2.5 mm
plating, insertion depth 8 mm, blue
Signal cable
Balanced twisted pair, 100 ohm,
(optional)
SFTP CAT5E, 0.53 mm, 24 AWG,
4 pairs, black, outdoor cable
Power cable
Electronic electric cable, 300
(optional)
V/500 V, 60227 IEC 10 (BVV), 3
x 2.5 mm
brown, blue, green-and-yellow), 27
A, outdoor cable, CCC, CE
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Hardware Installation Preparations
2
, black (five
2
,
2
, 0.02 m, 30 A,
2
, black (5
2
, 12.5 A, tin
2
, black (3 core wires:
Remarks
The length is
determined in presale
survey.
Dual power
supply: 2 PCS
Single power
supply: 1 PCS
Delivered with the
fittings
Delivered with the
fittings
Applicable to the dry
contact and RS485
connection, the
length is determined
by site survey.
1 PCS
The length is
determined by site
survey.
2
,
Delivered with the
fittings
2
,
Delivered with the
fittings
Delivered with the
fittings
Applicable to the dry
contact and RS485
connection, the
length is determined
by site survey.
1 PCS
The length is
determined by site
survey.
35