Huawei FusionModule2000 Installation Manual page 172

Smart modular data center, 2000 mm high cabinets, single-row aisle containment, 380 v
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Single-Row
Aisle Containment, 380 V)
Scenario
Figure 7-58 Layout of smart ETH gateways in scenario 2
Table 7-6 Scenario 3
Scenario
Rack environment unit deployed
Figure 7-59 Layout of smart ETH gateways in scenario 3
Issue 04 (2017-06-30)
No rack environment unit deployed
Module length > 7 m; number of air
conditioners > 4
When the smart module is 4 meters long or less, no multi-functional sensor is deployed in the
network cabinet.
When the smart module is longer than 7 meters, deploy one multi-functional sensor in the module
aisle (one more control skylight is required). Connect the multi-functional sensor to any smart ETH
gateway in the middle.
If the NetCol5000-A 35 kW air conditioner is connected, adjust the number of smart ETH gateways
according to the actual connection situation.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7 Installing Monitoring Devices
Rules for Deploying Smart ETH
Gateways
Deploy two smart ETH gateways for each
end cabinet and IT cabinet in the middle in
the smart module, not for other cabinets. A
total of six smart ETH gateways should be
deployed, as shown in Figure 7-58.
Rules for Deploying Smart ETH
Gateways
Deploy two smart ETH gateways for each
end cabinet and one smart ETH gateway for
every three cabinets among other cabinets in
the smart module, as shown in Figure 7-59.
163