FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Single-Row
Aisle Containment, 380 V)
Figure A-11 Installation position of the cabinet bottom sealing plate
(1) Column
Procedure
Step 1 Install the cabinet bottom sealing plate by following the instructions in 5.3.1 Installing a
Lower Mounting Kit for the End Door.
----End
A.4.4 Installing Sealing Plates Near the Aisle
Context
Because of the column, it is inevitable that certain cabinet places in the smart module are not
suitable for installing cabinets. Therefore, sealing plates need to be installed to ensure the air
tightness of the aisle containment.
Table A-2 Sealing plate types
Sealing Plate
300 mm wide, 2000 mm high sealing plate
Issue 04 (2017-06-30)
(2) Cabinet bottom sealing plate
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
BOM Number
21500707
A Appendix
216