Optional) Installing An Eth Converter - Huawei FusionModule2000 Installation Manual

Smart modular data center, 2000 mm high cabinets, single-row aisle containment, 380 v
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Single-Row
Aisle Containment, 380 V)
Procedure
Step 1 Use two M4x10 screw assemblies to secure the guide rail for the smart ETH gateway to the
planned position, as shown in Figure 7-60.
Step 2 Connect one end of the ground cable available in the smart ETH gateway package to the
ground point at the lower part of the cable trough using one M4 screw, and connect the other
end to the ground point on the side of the smart ETH gateway, as shown in Figure 7-60.
Step 3 Install the smart ETH gateway to the guide rail, as shown in Figure 7-60.
1.
2.
3.
----End

7.9.2 (Optional) Installing an ETH Converter

Prerequisites
An ETH converter should be installed for an air conditioner that does not support FE
communication. The ETH converter can be installed using the magnet on its rear.
Issue 04 (2017-06-30)
The M4 screw used for connecting the ground cable to the cable trough is available in the cable trough
package.
Align the upper slot of the guide rail for the smart ETH gateway with the upper part of
the guide rail, and pre-mount it onto the guide rail.
Press the lower part of the smart ETH gateway to clamp the ETH gateway onto the guide
rail.
Shake the smart ETH gateway in different directions to ensure that it is reliably installed.
Figure 7-60 Installing a smart ETH gateway
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7 Installing Monitoring Devices
164