ABB i-bus
KNX
Commissioning
Disable state on
KNX bus voltage recovery
Options:
Not disabled
Disabled
State before KNX voltage failure
This parameter defines the disable state after a KNX bus voltage recovery
Not disabled: The ballast/group is enabled after KNX bus voltage recovery and is no longer
subject to the Block. Any parametrized Staircase lighting or Slave functions will be active if they
were activated before the Block.
Disabled: The group/ballast is disabled after KNX bus voltage recovery and retains the
brightness value parametrized for this event.
State before KNX voltage failure: The ballast/group retains the state it was in before the KNX
voltage failure.
DG/S x.64.1.1 | 2CDC507164D0201 107