ABB i-bus KNX Product Manual page 153

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Enable function Inhibit/rest mode
object "Activate Inhibit/rest mode"
Options:
Linked group object:
Yes: The Inhibit/rest mode function and the Activate Inhibit/rest mode group object on the output are
enabled.
Whether or not an emergency lighting converter evaluates the group object and executes the
Inhibit/rest mode function is defined in the Emergency light x parameter window.
This means it is possible to deactivate the emergency lighting function so as to conserve the battery
charge e.g. during a construction/commissioning phase.
Enable fct Automatic emergency
lighting test
Object "Synch auto emergency
lighting tests"
Options:
Yes
No
Linked group object:
Yes: The gateway sends the start request for the automatic emergency lighting test to the
emergency lighting converter. The request is only sent to those converters to be included.
Settings for this are made in the Emergency light x parameter window using the parameters
Include in automatic function test or Include in automatic duration/partial duration test.
The automatic emergency lighting test is a standalone function on an emergency lighting
converter. The converter runs the tests cyclically based on its own stipulated timing. There is
no need for additional triggering via the gateway or an emergency lighting controller when
automatic testing is active. The test result is provided by the converter in the converter, read
by the gateway and sent on the KNX.
Note that there is a Pause between two DALI QUERY polls parameter in the A DALI
configuration parameter window. The longer the pause selected, the later the gateway will
read the test result from the converter.
No: The automatic emergency lighting test function is not enabled.
Yes
No
Note
Rest mode is a state in which the emergency light is switched off during its emergency lighting
operation.
Inhibit mode is a timed state in which the emergency light does not switch to emergency operation
in the event of a mains voltage failure.
Synchronize auto emergency lighting tests
Activate Inhibit/rest mode
DG/S x.64.1.1 | 2CDC507164D0201 151

Advertisement