ABB i-bus
KNX
Commissioning
...Recall scene
Options:
When the Slave function is activated, this parameter defines the reaction to a scene recall.
No reaction: A scene recall is ignored.
Function switches to standby: A scene recall ends the Staircase lighting function; the group executes
the recall. The Staircase lighting function switches to standby and waits for reactivation via the
Activate fct Staircase lighting group object or via an ON telegram on the Switch group object.
Reaction on KNX bus voltage recovery
and download
Options:
This parameter defines the state of the Staircase lighting function after a KNX bus voltage recovery or
a download.
The Staircase lighting function can be parametrized with the following states:
Not activated: The Staircase lighting function is not activated after KNX bus voltage recovery.
The group reacts like a normal group without an additional function.
Activated and in standby: The Staircase lighting function is activated after a download or
KNX bus voltage recovery and is in standby. The group can be reactivated by an ON telegram or via
the Activate fct Staircase lighting group object.
Activate and ON: The Staircase lighting function is activated and started after a download or after
KNX bus voltage recovery, i.e. the staircase lighting starts the time sequence.
State before failure: The Staircase lighting function retains the operating state (standby or not active)
that it had before download or KNX bus voltage recovery.
No reaction
Function switches to standby
Not activated
Activated and in standby
Activate and ON
State before failure