ABB i-bus KNX Product Manual page 41

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Enable DALI emergency lighting
converter (emergency lighting control)
Options:
Linked group object:
Yes: The DALI output supports control of DALI emergency lighting converters (type 1 DALI devices,
emergency lights with individual batteries to EN 62386-202). Corresponding parameter windows and
group objects are enabled. DALI addressing for the emergency lighting converters can be flexibly
handled in the ABB i-bus
each output. Individual DALI emergency lighting converters can be hidden in the A lighting converter
parameter window to provide a clear, compact parameter structure.
DALI emergency lighting converters can also be assigned to a DALI group for a clearer overview.
Again, in such cases the converters can only be controlled individually. They have no group function.
No: Emergency lighting converter control is not supported on the DALI output. No corresponding
parameter windows and group objects are enabled, so the ETS parameter structure here is very
concise.
Enable DALI scenes
(scene control)
Options:
Linked group object:
Yes: The DALI output supports control for up to 16 DALI scenes. The corresponding parameter window
x scenes and the Scenes 1...16 group object are enabled.
There are 16 DALI light scenes available on each DALI output; these can be assigned to any of the
16 KNX scenes. So for example, DALI scene 8, which is parametrized in the DALI gateway, can be
assigned to KNX scene 35 and recalled or saved using the KNX scene commands for scene 35.
No: The DALI output does not support the Scenes function. No corresponding parameter windows and
group objects are enabled, so the ETS parameter structure here is very concise.
Note
Scene numbers 1 to 16 shown in the gateway are mapped to scenes 0 to 15 on the DALI.
Yes
No
®
Tool. Up to 64 DALI emergency lighting converters can be connected to
Yes
No
Various "Output X ballast Y" group objects
Scenes 1...16
DG/S x.64.1.1 | 2CDC507164D0201 39