Commissioning
Extend staircase lighting on
repeated switch on
Options:
If a further ON telegram is received via the Switch object during the staircase lighting sequence (including
dimming down/advance warning), the remaining staircase lighting time can be extended. This is possible
by repeated operation of the push button ("pumping up") until the maximum parametrized number of
retriggering operations is reached. The maximum time can be set to 1, 2, 3, 4 or 5 times the staircase
lighting time.
Let's say the staircase lighting time has been extended to the maximum time by pumping up. If some of
the time has already elapsed, the staircase lighting time can be extended to the maximum time again by
pumping up.
However, the parametrized maximum time may not be exceeded.
No: Incoming ON telegrams are ignored. The staircase lighting time continues unmodified to
completion.
Yes - restart staircase lighting time (retrigger): The staircase light time is reset with each new ON
telegram and starts to count again. This option allows the process to be repeated as often as desired.
Yes - Extend staircase lighting time up to max 2/3/4/5 x (pumping up): New ON telegrams extend the
staircase lighting time by 2/3/4/5 times.
128 2CDC507164D0201 | DG/S x.64.1.1
No
Yes - restart staircase lighting time (retrigger)
Yes - Extend staircase lighting time up to max 2 x (pumping up)
Yes - Extend staircase lighting time up to max 3 x (pumping up)
Yes - Extend staircase lighting time up to max 4 x (pumping up)
Yes - Extend staircase lighting time up to max 5 x (pumping up)