Slave Template (Group X/Ballast X) Parameter Window - ABB i-bus KNX Product Manual

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
3.2.4.4
X Slave template (group x/ballast x) parameter window
The parameter window is enabled if the Enable additional function parameter in
Parameter_window_x_group_group_x, p. 135 has been set to Slave.
When the Slave function is operational, the group follows the brightness value provided by a master via
the Brightness value of slave group object. Alternatively, the master can be a ballast or group connected to
the same gateway output, in which case the brightness value of the slave can be sent direct to the slave
internally.
Reaction to Switch on, Dim, Brightness value, Relative dimming or Recall scene telegrams can be
individually parametrized.
As the function and the parameter window for the group and the ballast are identical, only the group is
referred to below. Group can be substituted with ballast.
Using the Slave function, each individual group on the gateway can be integrated into constant lighting
control implemented for example by an ABB i-bus
The operating state of the slave after a download or KNX bus voltage recovery can be parametrized.
112 2CDC507164D0201 | DG/S x.64.1.1
®
light controller or KNX presence detector as a master.