ABB i-bus KNX Product Manual page 23

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Device technology
Triggering DALI addressing via the
Press push button
DALI addressing. The yellow DALI LED flashes. DALI devices without addresses are assigned the first
free address. If the system detects devices with duplicate DALI addresses, it deduplicates them.
Manual operation including triggering DALI addressing can be enabled or disabled via the Disable manual
operation/Status group object (no. 2). The status of whether manual operation is disabled can be
requested via the same group object. After a KNX voltage failure, the system reinstates the state prior to
the failure. The timeout for manual operation before automatic exit is parametrizable. This time is
retriggered after every manual operation.
Note
i-bus
commissioning.
We recommend that you do not use the i-bus
functions can have a mutual influence.
Note
KNX commands incoming during manual operation are not executed, but are processed in the
background. Scene implementation and interim dimming values are not taken into consideration in the
background in the simulation.
Depending on the parametrization (see General parameter window), the system sets either the updated
brightness value or the brightness value set in manual mode.
Note
The Forced operation and Block function of a group has a higher priority than manual operation, i.e. if a
ballast or group with a particular brightness value is forcibly operated or blocked, it cannot be manually
switched or dimmed. If the forced operation or block is reset in manual mode, the ballast or group stays
at the current brightness value regardless of what it is programmed to do when forced operation ends,
and only follows the next control command.
for longer than five seconds. This will not exit the current mode but will trigger
®
Tool functions are carried out during manual operation in order to ensure consistent
push button:
®
Tool and manual operation at the same time as the
DG/S x.64.1.1 | 2CDC507164D0201 21