ABB i-bus KNX Product Manual page 57

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Enable Group object
"Status brightness value"
Options:
Linked group object:
The parameter defines how the current status of the DALI output brightness value is sent on the KNX.
Yes: The (DALI output X) Status brightness value group object is enabled for the brightness value.
No: The brightness value is not actively sent on the KNX.
Yes
No
Selection of Yes option:
Dependent parameters:
Send object value
Options:
On change
On request
After a change or on request
On change: The status is sent when a change occurs.
On request: The status is sent when a request occurs.
After a change or on request: The status is sent when either a change or request occurs.
Send interim values on transfers
(e.g. Dim up, scene transfer)
Options:
No
Yes
This parameter defines whether the brightness value status is only sent at the end of the brightness
value transition or whether interim values are sent.
No: The brightness status is sent on the KNX once the final brightness value has been
reached.
Yes: The brightness value status is also sent during a brightness value transition.
Selection of Yes option:
Dependent parameters:
Send interval
Options:
0...2...65,535 s
This parameter defines the send interval for the brightness value status during a brightness
value transition (e.g. dimming up, scene transition).
Status brightness value
DG/S x.64.1.1 | 2CDC507164D0201 55

Advertisement

Table of Contents
loading

Table of Contents