ABB i-bus KNX Product Manual page 62

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Enable Group object
"DALI voltage fault"
Options:
Linked group object:
This group object indicates a DALI voltage fault. The fault may be a surge, overload or short circuit. For
more detailed information please see the Output X Status byte group object.
Yes: The group object is enabled.
No: The group object is not enabled.
Enable Group object
"Lamp fault"
Options:
Linked group object:
This group object indicates a fault on a lamp for the DALI output.
Yes: The group object is enabled.
No: The group object is not enabled.
Note
A ballast fault takes priority over a lamp fault. The ballast fault masks and hides the lamp fault.
60 2CDC507164D0201 | DG/S x.64.1.1
Yes
No
Selection of Yes option:
Dependent parameters:
Send object value
Options:
On change
On request
After a change or on request
On change: The status is sent when a change occurs.
On request: The status is sent when a request occurs.
After a change or on request: The status is sent when either a change or request occurs.
Yes
No
DALI voltage fault
Lamp fault