Commissioning
No: The Inhibit/rest mode function is not enabled for the output.
152 2CDC507164D0201 | DG/S x.64.1.1
Danger
In both cases, the emergency light no longer fulfils its safety function and remains off.
For this reason, use this function with great care. It can be helpful to use Inhibit/rest mode during
the construction phase when the power supply is often switched off, to prevent the emergency
lighting battery from constantly charging/discharging and thus conserve the emergency light.
Selection of Yes option:
Dependent parameters:
Automatically exit
Inhibit/rest mode after
Options:
0...8...48 h
This parameter defines how long the emergency lighting converter stays in Inhibit/rest mode.
There will be no emergency lighting function during this time. The emergency lighting converter
does not switch on the emergency lighting in the event of a mains voltage failure.
Note
The time interval is 15 minutes. The gateway repeats the DALI Inhibit and Rest command
for the emergency lighting converter approximately every 5 minutes.
Send status Inhibit/rest mode
Options:
No
Yes
Linked group object:
Yes: The Activate emergency lighting Inhibit/rest mode/Status group object not only activates
the mode but also displays the status, i.e. whether at least one emergency lighting converter
on the output is in Inhibit/rest mode. Information on individual emergency lighting converters is
determined by the Emergency lighting converter status group object.
No: No Inhibit/rest mode activation status is sent on the KNX.
Activate emergency lighting Inhibit/rest mode/Status