ABB i-bus KNX Product Manual page 212

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
928, 931... Trigger em lighting test/Status
This group object is enabled if an Emergency light x is enabled in X lighting converter/Emergency light template parameter
window, p. 155. The object can adopt one of 3 data formats. The data format is defined in the A lighting converter, Emergency
light x parameter window by setting the Enable Group Objects "Trigger em lighting test" parameter to Yes, DGN/S 1.16.1
format with status.
This group object triggers an emergency lighting test for emergency light x. At the same time, the result of the emergency
lighting test can be requested via this group object and sent on the KNX.
The test result is sent on the KNX with the following coding.
The following numbering applies to the list below:
2
The bit number is identical to the exponent of the bit, e.g. number 2 corresponds to 2
Bit 0...2
Bit 3 and 4
Bit 5
Bit 6
Bit 7
If a new test is requested on the group object before the ongoing test has ended, this is immediately interrupted and the new
test is requested. This is also the case when the ongoing test is requested again.
Bit 6 and 7 only relate to an emergency lighting converter. If the device is a normal DALI device, bit 6 and 7 are not evaluated.
2)
See Application Notes 166/14v03 para. 2.8.2.5 LEGACY CTTS
210 2CDC507164D0201 | DG/S x.64.1.1
Function
(DGN/S)
7
6
5
4
3
2
2
2
2
2
2
= 000, stops the test currently running
= 001, result relates to the function test
= 010, result relates to the partial duration test
= 011, result relates to the duration test
= 100, result relates to the battery query
= 101 and 110, without function or not taken into account in evaluation
= 111, there is no valid test state or the queried DALI device does not support DALI Standard
IEC 62386-202 for emergency lighting converters. The content of the other bits is invalid.
= 00, testing has ended positively
= 01, testing pending, not yet started
= 10, test running
= 11, test interrupted
= 1, testing manually started
= 1, lamp fault (emergency lighting converter)
= 1, device (emergency lighting converter) fault
Group object name
Output A - Emergency light x
1
0
2
2
Data type
Flags
1 byte
C, R, W, T
2)
Non DPT
2
.