Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
48, 59...
224, 235...
This group object is always enabled if a group or ballast is in use.
This group object consists of two bytes. Each bit contains a group or ballast status.
The following numbering applies to the list below:
High byte
15
2
The bit number is identical to the exponent of the bit, e.g. number 2 corresponds to 2
Bit 0:
Bit 1:
Bit 2:
Bit 3:
Bit 4:
Bit 5:
Bit 6:
Bit 7:
Bit 8:
Bit 9:
Bit 10:
Bit 11 to 15
For groups, the group status is generated by the OR combination of the individual devices in the group.
The telegrams are sent as soon as the status is detected.
200 2CDC507164D0201 | DG/S x.64.1.1
Function
Status byte
Dependent on parameter
14
13
12
11
10
9
2
2
2
2
2
2
1 = Ballast switch status ON
0 = Ballast switch status OFF
For groups: the switch status is 1 if at least one device in the group is ON. 0 if all group devices are OFF.
1 = ballast monitored
0 = ballast not monitored
For groups: 1 if all devices in the group are monitored. 0 if at least 1 device is not monitored.
1 = ballast unavailable, i.e. not responding to DALI QUERY requests
0 = ballast available, i.e. responding to DALI QUERY requests
For groups: 1 if at least 1 device in the group is not available. 0 if all devices in the group are available.
1 = ballast/group is in blocked state
0 = ballast/group is not in blocked state
1 = ballast/group is in forced operation state
0 = ballast/group is not in forced operation state
1 = ballast/group has activated an additional function and is in standby or running
0 = ballast/group has not activated additional function
1 = ballast/group has activated an additional function and is running
0 = ballast/group has not activated additional function
1 = Ballast burn-in function active
0 = Ballast burn-in function not active
For groups: 1 if at least 1 device in the group is in burn-in state. 0 if no devices in the group are in burn-in
state.
1 = ballast has a lamp fault
0 = ballast has no lamp fault
For groups: 1 if at least 1 device in the group has a lamp fault. 0 if no devices in the group have a lamp
fault.
1 = ballast has a ballast fault
0 = ballast has no ballast fault
For groups: 1 if at least 1 device in the group has a ballast fault. 0 if no devices in the group have a
ballast fault.
1 = ballast/group turn off brightness active
0 = ballast/group turn off brightness not active
0, not in use
Group object name
Output A - Group x
Output A - Ballast x
Use group x
Use ballast x
Low byte
8
7
6
5
4
2
2
2
2
2
2
Data type
2 byte
Non DPT
3
2
1
0
2
2
2
2
.
Flags
C, R, T