KNX
Commissioning
3.3.4

Group x/Ballast x group objects

As the lighting groups (groups) and individual DALI devices (ballasts) have the same functions and group
objects, this chapter describes them jointly. The object names are distinguished by the term 'group' or
'ballast'.
If their functions differ, this is specified.
In the No. column (object number) the first line gives the object numbers for the first two groups and the
second line those for the first two ballasts.
The group object numbers for groups 3...16 and ballasts 3...64 are multiples of the first two object
numbers.
Likewise, references to a group or ballast parameter window only differ by name – group, or ballast.
References to a group in this section mean a DALI group.
Output B, the second DALI output on the DG/S 2.64.1.1, is a mirror image of output A as described in this
section. Therefore output B has the same group objects as output A; only the names differ.
Output A group object names:
Output A - Group x
Output A - Ballast x
Output A - Emergency light x
Output B group object names:
Output B - Group x
Output B - Ballast x
Output A - Emergency light x
Note
Ballasts are assigned to a DALI group by means of the i-bus
commissioning tool which can be used to change DALI device numbers and make group assignments.
The tool can also test functions and read operating states.
If a DALI device is controlled individually, it cannot also be assigned to a DALI group. A DALI device can
be controlled either individually via ballast commands, or in a group via group commands. Overlapping
DALI groups are not supported.
®
Tool. This is a diagnostics and
DG/S x.64.1.1 | 2CDC507164D0201 199