ABB i-bus
KNX
Planning and application
The following table shows the reaction to incoming telegrams when the Slave function is parametrized.
Operating situation
or
Group objects
Download (start)
Download (end)
voltage failure
KNX bus
voltage
recovery
DALI
voltage failure
or
Gateway
supply
ballast recovery
ON
Switch
OFF
Relative dimming
Brightness value
Recall scene
Brightness value of slave
0
Slave
function
activate
1
ON
Forced
operation/Block
OFF
ON
Partial failure
OFF
218 2CDC507164D0201 | DG/S x.64.1.1
Inactive
(Activate fct
Slave = 0)
Parametrizable – group x/ballast x Fault – Min/Max/OFF/No change
- Mode: Group x/Ballast x Slave – Inactive/Standby/Active and on/State before failure
- Group x/Ballast x Fault – Min/Max/OFF/No change/State before failure
Group x/Ballast x Fault – Min/Max/OFF/No change
- Group x/Ballast x Fault – Min/Max/OFF/No change/Actual KNX target state
Switch-on value
OFF/Turn off value
Dimming
Brightness value
Scene
No reaction
No reaction
Parametrizable:
Group x/Ballast x Slave
- Activate and ON/standby
Forced brightness set. Forced operation has the highest priority.
Actual KNX target state set
Partial failure value set. Partial failure takes priority over additional function.
Actual KNX target state set
Additional function Slave
Active in standby
(Activate slave mode = 1)
Such as KNX bus voltage failure
Such as KNX bus voltage recovery
Slave function discontinued
Parametrizable:
Parametrizable:
Slave function discontinued
Parametrizable:
→ Active,
current Brightness value of slave
is set
OFF/Turn off value,
remains in standby
Dimming, remains in standby
Brightness value, remains in
standby
Scene
No reaction
→ Inactive
Parametrizable:
Group x/Ballast x Slave
- Activate and ON/standby
Active, actual KNX target state set (standby or ON)
Active, actual KNX target state set (standby or ON)
Active and ON (running)
(Function = 1)
Parametrizable:
Group x/Ballast x Slave
- No reaction/standby turn on brightness
OFF and goes to standby
Parametrizable:
Group x/Ballast x Slave
- No reaction/dimming standby
Parametrizable:
Group x/Ballast x Slave
- No reaction/brightness value standby
Parametrizable:
Group x/Ballast x Slave
- No reaction/scene and standby
Brightness value of slave 

is set
→ Inactive
Parametrizable:
Group x/Ballast x Slave
- Activate and ON/standby