ABB i-bus KNX Product Manual page 36

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Enable Group object
"Gateway supply voltage fault"
Options:
Linked group object:
Yes: The Gateway supply voltage fault group object is enabled. As soon as the device supply voltage
is interrupted, the Gateway supply voltage fault group object sends a telegram with the value 1 on the
KNX. The time at which a telegram is sent can be adjusted using the parameter below.
No: The gateway supply voltage failure is not signaled to the KNX.
34 2CDC507164D0201 | DG/S x.64.1.1
Yes
No
Selection of Yes option:
Dependent parameters:
Send object value
Options:
On change
On request
After a change or on request
On change: The status is sent when a change occurs.
On request: The status is sent when a request occurs.
After a change or on request: The status is sent when either a change or request occurs.
Enable acknowledgement via object
"Acknowledge gateway supply
voltage fault"
Options:
Yes
No
Linked group object:
Yes: The Acknowledge Gateway supply voltage fault group object is enabled. The fault is only
reset by an acknowledgment (a telegram with the value 1) via this group object,
®
or via the i-bus
Tool.
No: The Gateway supply voltage fault group object requires no acknowledgement. The group
object value is updated when a change occurs.
Gateway supply voltage fault
Acknowledge gateway supply voltage fault