ABB i-bus KNX Product Manual page 134

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Reaction on activation via object
"Activate fct Staircase lighting"
Options:
This parameter defines the state of the Staircase lighting function after it has been activated by the
Activate fct Staircase lighting group object.
Activated and in standby: The Staircase lighting function switches to standby when activated via the
Activate fct Staircase lighting group object. In other words, the staircase lighting waits for an ON
telegram which triggers it.
Activate and ON: The Staircase lighting function switches on immediately when activated via the
Activate fct Staircase lighting group object. In other words the staircase lighting starts the time
sequence.
132 2CDC507164D0201 | DG/S x.64.1.1
Activated and in standby
Activate and ON
Note
The ON function via the Activate fct Staircase lighting group object has no effect on the
extension (pumping up) of the staircase lighting time.