ABB i-bus KNX Product Manual page 172

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Note
Even if the scene values are not overwritten after a download, the scene members have to be selected
in order to tell the gateway which ballasts or groups are members of the scene.
Note
When a download occurs, the parametrized scene values are usually transferred to the gateway. Note
that if no change has been made in the ETS application, ETS does not transfer these values again
when a partial ETS download occurs. To transfer the values to the gateway even when no parameters
have been changed, run a normal download using "Program application program".
Group x brightness value of scene or
Ballast x brightness value of scene
Options:
This parameter defines the brightness value to which scene members are set when a scene is recalled.
No change (not a member in this scene): The ballast or group is not part of this scene and is not
affected by a scene recall. The current brightness value of remains unchanged and even when the
scene is stored via the KNX, the brightness value is not stored in the ballast.
100% (255)...0% (OFF): The ballast or group is part of the scene. During a scene recall, the scene
member is set to the brightness value parametrized here. If the set brightness value is above or below
the maximum brightness or minimal dimming value defined for the scene member in question, the
corresponding dimming value is stored in the scene.
170 2CDC507164D0201 | DG/S x.64.1.1
No change (not a member in this scene)
100% (255)
99% (252)
...
1% (3)
0% (OFF)