ABB i-bus KNX Product Manual page 120

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
With active additional function.
Reaction on...
...Switch on
Options:
When the Slave function is activated, this parameter defines the reaction to an ON telegram on the Switch
group object.
No reaction: An ON telegram on the Switch group object is ignored.
Function switches to standby: An ON telegram on the Switch group object puts slave mode in
standby. The group executes the Brightness value telegram via the Brightness value group object.
The Slave function is latent and waits for reactivation via the Activate fct Slave group object or via an
ON telegram on the Switch group object.
Note
The reaction to an OFF telegram on the Switch group object cannot be parametrized.
An OFF telegram always interrupts the Slave function. The Slave function switches to standby mode, in
which the brightness values on the Brightness value of Slave group object are ignored.
The Slave function is reactivated when an ON telegram is received on the Switch group object.
The reaction to a telegram with the value 1 received on the Activate fct Slave group object can be
parametrized (see X Slave template (group x/ballast x) parameter window, p. 112.)
118 2CDC507164D0201 | DG/S x.64.1.1