ABB i-bus
KNX
Commissioning
No.
31
This group object is enabled if the Enable function "Partial failure" parameter is set to Yes in the X Output: Functions
(Turn off brightness/Burn-in/Slave offset/Partial failure) parameter window, p. 67.
This group object sends information on the KNX indicating a partial lighting failure on output A.
Telegram value:
31
This group object is enabled if the Enable function "Partial failure" and Externally via object "Activate partial failure/Status"
parameters are both set to Yes in X Output: Functions (Turn off brightness/Burn-in/Slave offset/Partial failure) parameter
window, p. 67.
This group object sends (status) information on the KNX from the gateway, indicating a partial lighting failure.
It also receives information via the KNX that there is a partial failure, so that the gateway triggers a partial failure on output A.
Telegram value:
32
Group object is not assigned.
Function
Status Partial failure active
Dependent on parameter
1 = Partial failure active
0 = Partial failure inactive
Note
What constitutes a partial failure for the DALI output can be defined in the A Output Functions parameter window.
•
Gateway supply voltage failure
•
Emergency lights in emergency mode
•
Lamp/ballast fault
•
Externally signaled via the Activate partial failure/Status object
How the group or an individual ballast reacts to a partial failure is defined in the Group functions or Ballast functions
parameter window.
Activate partial failure/Status
Dependent on parameter
1 = Activate partial failure
0 = Deactivate partial failure
Note
What constitutes a partial failure for the DALI output can be defined in the A Output Functions parameter window.
The criteria are:
•
Gateway supply voltage failure
•
Emergency lights in emergency mode
•
Lamp/ballast fault
•
Externally signaled via the Activate partial failure/Status object
How the group or an individual ballast reacts to a partial failure is defined in the Group functions or Ballast functions
parameter window.
blank
Group object name
Output A
Enable function "Partial failure"
Output A
Externally via object "Activate partial failure/Status"
DG/S x.64.1.1 | 2CDC507164D0201 191
Data type
Flags
1 bit
C, R, T
DPT 1.010
1 bit
C, R, W, T
DPT 1.010