Commissioning
Dim period to reach basic brightness
Options:
0...2...65,535 s
This parameter is used to set a dimming transition to the basic brightness for the staircase lighting.
Note
When setting dimming times of less than 32 seconds, note that they will be mapped to
the nearest DALI fade time. The conversion is as follows:
Turn on
brightness
in 1 s
0
1
2
3
4
5 and 6
7...9
10...13
14...18
19...26
27...32
> 32...65,535
The fade time is specified as the time required to change the lamp power from the
current brightness value to the required target brightness.
If a lamp is switched off, the preheat and ignition time are excluded from the fade
time.
Basic brightness hold time
(0 = infinite)
Options:
0...10...65,535 s
This parameter defines how long the group is maintained at the basic staircase lighting brightness
before it is finally switched off or set to the turn off brightness. This time can be indefinite.
1...65,535 s: During this time, the group maintains the basic brightness before finally switching
off.
0 s: The hold time is indefinite, i.e. the group does not switch off and remains at the basic
brightness.
Fade time in s
acc. to EN 62386-102
jump to
1.0
2.0
2.8
4.0
5.7
8
11.3
16.0
22.6
32.0
Time values with an error tolerance of ±3 s
DG/S x.64.1.1 | 2CDC507164D0201 127