®
ABB i-bus
KNX
Commissioning
Prolong Time at end of
emergency lighting operation
Options:
This parameter defines in minutes how long the emergency light remains on at this brightness value when
emergency mode ends, before it is re-enabled for KNX telegrams.
Time limit for triggering
emergency lighting test
Options:
A converter may not always be able to implement a requested emergency lighting test immediately –
for example because the battery charge is low.
This parameter defines a time span (TEST EXECUTION TIME TIMEOUT) in days, within which the test
must be run. This time is stored in the emergency lighting converter and evaluated.
A setting of 0 means that the emergency lighting test must be run within 15 minutes.
Note
The state indicating whether an emergency lighting test is pending, running or complete is sent via
group objects (e.g. Emergency lighting converter status or Em lighting test status (addr)), or can be
queried if necessary.
0...127 min
0...7...255 d
DG/S x.64.1.1 | 2CDC507164D0201 157