ABB i-bus KNX Product Manual page 199

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
42
This group object is enabled if the Em lighting test result (addr) parameter is set to Yes in the X lighting converter parameter
window, p. 149.
This group object consists of 4 bytes. The individual bytes contain information about a DALI emergency lighting converter.
If a normal DALI device is queried, bit 15 is set to value 1. The other bits are invalid.
The sending behavior for this group object is defined in the Emergency light parameter window.
The following numbering applies to the list below:
31
2
15
2
The bit number is identical to the exponent of the bit, e.g. number 2 corresponds to 2
Bit 0...5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13...14
Bit 15
Bit 16...23
Bit 16
Bit 17
Bit 18
Bit 19
Bit 20
Bit 21
Bit 22
Bit 23
Bit 24...31
43
This group object is enabled if the Stop all em lighting tests parameter is set to Yes in the X lighting converter parameter
window, p. 149.
Telegram value:
Function
Em lighting test result
Dependent on parameter
30
29
28
27
26
25
2
2
2
2
2
2
14
13
12
11
10
9
2
2
2
2
2
2
= contains the binary number (0...63). This number is the number of the DALI device that the High byte
information relates to, plus 1.
= 0 indicates that the information concerns an individual emergency lighting converter
= 1, status value request. If a telegram with a set bit 7 is received, it is interpreted as a request for
various status messages about the DALI device and corresponding feedback is sent. When the
answer is returned, the value of bit 7 is set to 0.
= 1, last test was a function test
= 1, last test was a partial duration test
= 1, last test was duration test
= 1, if there is at least one fault in bit 16...23 or it is not possible to poll the emergency lighting converter
battery
= 1, battery query finished (must be supported by the converter, optional only in DALI standard)
= 0, without function
= 1, there is no valid test state or the queried DALI device does not support DALI Standard IEC 62386-
202 for emergency lighting converters. The content of the other bits is invalid.
= correspond to DALI telegram 252 ("query failure status")
= 1, switching defective. The emergency lighting converter did not respond during the test.
= 1, battery fault (battery fully discharged before rated operating time completed)
= 1, battery defective, battery fault
= 1, emergency lighting lamp fault
= 1, function test was triggered but could not be started in the predefined time
= 1, duration test was triggered but could not be started in the predefined time
= 1, function test fault, fail
= 1, duration test fault, fail
= Depending which test has been undertaken, this highest byte contains the battery charge state
(0...255 = 0...100%) or the duration of the test until the battery was discharged. The value
corresponds to the time in 2 x min.
Stop all em lighting tests
Dependent on parameter
1 = All emergency lighting tests are stopped
0 = No function
Group object name
Output A
Em lighting test result (addr)
24
23
22
21
20
2
2
2
2
2
2
8
7
6
5
4
2
2
2
2
2
2
Output A
Stop all em lighting tests
Data type
4 byte
non DPT (FEOT)
19
18
17
16
2
2
2
High Byte
3
2
1
0
2
2
2
Low Byte
2
.
1 bit
DPT 1.010
DG/S x.64.1.1 | 2CDC507164D0201 197
Flags
C, R, W, T
C, W, T

Advertisement

Table of Contents
loading

Table of Contents