ABB i-bus KNX Product Manual page 197

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
40
This group object is enabled if the Trigger em lighting test (addr) parameter is set to Yes in the X lighting converter parameter
window, p. 149.
This group object triggers an emergency lighting test. It does not send the status or the emergency lighting test result from the
gateway on the KNX.
This group object consists of two bytes.
-
-
The following numbering applies to the list below:
High byte
15
2
The bit number is identical to the exponent of the bit, e.g. number 2 corresponds to 2
Bit 0...5
Bit 6
Bit 7
The value of the High byte contains the information on which emergency lighting test to trigger.
Value 0 (000)
Value 1 (001)
Value 2 (010)
Value 3 (011)
Value 0 (000)
Value 5 (101)
Value 6 (110)
Value 7...255
Function
Trigger em lighting test (addr)
Dependent on parameter
The High byte contains a numeric value that determines which emergency lighting test to trigger.
The Low byte contains the number of the emergency lighting converter.
14
13
12
11
10
9
2
2
2
2
2
2
= contains the binary number (0...63). This number is the number of the DALI emergency lighting
converter (Emergency light x) that the High byte information relates to, plus 1.
= 0
= 1
= Reserved, no function
= Function test requested (corresponds to DALI Cmd 227)
= Duration test requested (corresponds to DALI Cmd 228)
= Partial duration test requested
= Stops the test currently running (corresponds to DALI Cmd 229)
= Function test flag reset (corresponds to DALI Cmd 230). This means that if a function test is requested
and cannot executed, a flag is set in the emergency lighting converter indicating that the test is
pending. This flag can be canceled so that a function test is no longer pending.
= Duration test flag reset (corresponds to DALI Cmd 231). This means that if a duration test is requested
and cannot executed, a flag is set in the emergency lighting converter indicating that the test is
pending. This flag can be canceled so that a duration test is no longer pending.
= Reserved, no function
Note
The result of the emergency lighting test for each converter can also be sent via the addressed group object Em
lighting test result (no. 42) or the Em lighting test status group object (no. 929ff).
Group object name
Output A
Trigger em lighting test (addr)
Low byte
8
7
6
5
4
2
2
2
2
2
2
Data type
2 byte
DPT_CTC
3
2
1
0
2
2
2
2
.
DG/S x.64.1.1 | 2CDC507164D0201 195
Flags
C, W, T

Advertisement

Table of Contents