Commissioning
Note
Flexible dimming time is received via the Output x Flexible time for dimming/fade time group object and
affects various output functions:
To use the Flexible dimming time function you first need to enable the output's Flexible time for
dimming/fade time group object in the A Output/Functions parameter window. You also need to select
the function for the parameter that can be changed via KNX. We recommend that you only change one
time via KNX. Otherwise the dimming time has to be rewritten on the ballast every time a function is
called, which impairs function performance.
114 2CDC507164D0201 | DG/S x.64.1.1
Dimming time for turn on/off value
Dimming time for brightness value
Dimming time for slave brightness value
Scene transition time
Selection of Fixed fade time option:
Dependent parameters: