ABB i-bus KNX Product Manual page 60

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Acknowledge fault messages
Enable Group object
"Acknowledge fault messages/Status"
Options:
Linked group object:
This parameter enables the Acknowledge faults function and its required group object.
Yes: The Acknowledge faults function and its required group object are enabled.
No: The Acknowledge faults function and group object are not enabled.
Fault messages are usually automatically reset once the fault has been corrected. With the Acknowledge
faults function, the message is only cleared by acknowledgment. Only then is a telegram with the value 0
sent via the group object for the corresponding fault type. This function can be very helpful when detecting
sporadic faults or events which take place during unmanned monitoring periods.
Note
The Acknowledge faults function relates to the whole DALI output and fault messages for ballasts and
groups, with the exception of the gateway supply voltage fault, which can be acknowledged separately.
58 2CDC507164D0201 | DG/S x.64.1.1
Yes
No
Acknowledge fault messages/Status