Commissioning
3.2.7.1
X scenes/Scene x parameter window
This parameter window is visible if DALI scene x is assigned to a KNX scene in the X scenes parameter
window.
The properties of the scenes and their members are parametrized in this window. A scene member can be
any ballast or group on the DALI output.
Note
All the theoretically possible groups and ballasts are shown in this parameter window. The person
commissioning the system must ensure that the required members are also connected to the output.
ETS and the gateway do not check this.
Transition time for scene
Options:
This parameter defines how long it takes for scene members to reach their scene value (brightness value)
after a scene is recalled. If the dimming process is complete, the scene members have reached the set
brightness for the scene. These times are specified by the DALI standard and are stored in the ballast.
Example
Group 1, which is dimmed from 10% to 100%, and ballast 2, which is dimmed from 90% to 100%, reach
the set brightness value of the scene simultaneously.
168 2CDC507164D0201 | DG/S x.64.1.1
Jump to
0.7 s
2.0 s
...
90.5 s
Via object "Flexible time for dimming/fade time"